Levelflex M FMP40 FOUNDATION Fieldbus Wiring
Endress+Hauser 35
Wiring in T12 housing
L00-FMP41Cxx-04-00-00-en-006
-
-
5
12
3
4
"
3
4
1
2
-+
2
4
3
Made in Germany
D-79689 Maulburg
Dat./Insp.:
Order Code:
IP68 / NEMA 6P
Ser.-No.:
4-wire
ENDRESS+HAUSER
t >85°C
TA > 70°C :
D01301-A
if modification
see sep. label
X=
Patents
LEVELFLEX-M
90 … 253 V AC 1VA
10,5 … 32 V DC 1W
16 … 3 V DC 0,8W
Profibus PA
Fieldbus
FOUNDATION
LN= PN=
4 … 20 mA HART 2-wire
1
When you use the measuring system in hazardous areas, make sure you comply with
national standards and the specifications in the safety instructions (XA’s).
Make sure you use the specific cable gland.
Connect up the Levelflex M as follows:
Before unscrew housing cover (2) at seperate connection room
turn off the power supply!
Insert cable (3) through gland (5).
Use screened, twisted wire pair.
Only ground screening of the line (5) on sensor side.
Make connection (see pin assignment).
Tighten cable gland (4).
Screw on housing cover (2).
Switch on power supply.
●
●
●
●
●
Before connection please note the following:
FOUNDATION Fieldbus devices are marked on the
nameplate (1). The voltage is determined by the
FOUNDATION Fieldbus standard and the desired safety
concept. (see chapter 4.3).
Connect potential matching line to transmitter earth terminal
before connecting up the device.
Tighten the locking screw:
It forms the connection between the probe and the housing
earth potential.
●
●
Caution!
plant
ground