Mapping is also possible by manually entering the range to be suppressed. This entry is made in the
"range of mapping" (052) function.
"
Caution!
The range of mapping must end 0.3 m (20") before the echo of the actual level.
Probe free
If the probe is uncovered, mapping is carried out along the whole probe length.
"
Caution!
Only begin mapping in this function if the probe is definitely uncovered. Otherwise, the device will
not measure correctly!
Function "range of mapping" (052)
This function displays the suggested range of mapping. The reference point is always the reference
point of the measurement (→ ä 54). This value can be edited by the operator.
For manual mapping, the default value is 0.3 m.
Function "start mapping"(053)
This function is used to start the interference echo suppression up to the distance entered in "range
of mapping" (052).
Options:
• off: no mapping is carried out
• on: mapping is started
⇒