Operation Liquistation CSF34
136 Endress+Hauser
Example of a cleaning phase table
# Duration (s) Water Info
1 5 0 Arm at tundish
2 5 1 Water valve
3 5 0 Drip time
The distribution arm only goes to the bottle at the next sampling.
MenuSetup/Inputs/Additional functions/Cleaning/Cleaning 1/Chemoclean Plus/ChemoCleanPlus setup
Function Entry for sample program
Cleaning cycle Off
Only active via external controller.
Start signal Binary input
Select the sensors and their measured variables that should be used
as the minuend (Y1) or subtrahend (Y2).
Start signal Binary input
The input must be selected beforehand.
Outputs
OutputRelay Cleaning
Assignment Cleaning 1 - Out 1 Press the navigator to confirm.
4. Please check the function in Menu/Setup/Output/Relay %0V .
10.6.4 Other settings and manual cleaning
Menu/Setup/Additional functions/Cleaning/Cleaning 1 ... 4
Function Options Info
Start signal Selection
None
Fieldbus signals
Signals of digital or
analog inputs
Factory setting
None
In addition to cyclic cleaning, you can also use an
input signal to start event-controlled cleaning.
Choose the trigger for such a cleaning
process here.
Interval and weekly programs are executed as
normal, i. e. conflicts can occur. Priority is given
to the cleaning program that was the first to be
started.
Hold Selection
Off
On
Factory setting
On
Decide whether there should be a hold
during the cleaning process. This hold
affects the inputs to which this cleaning
process is assigned.
Start single Action Start an individual cleaning process with the
selected parameters. If cyclical cleaning is
enabled, there are times in which it is not
possible to manually start the process.
Stop or Stop failsafe Action End the cleaning process (cyclically or manually)
Outputs Goes to the menu Outputs
Cleaning program
assignment view
Shows an overview of the cleaning processes

Table of Contents