EasyManua.ls Logo

Endress+Hauser Liquistation CSF34 - Technical Data: Ethernet, Current Outputs, and Electrical Specs

Endress+Hauser Liquistation CSF34
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data Liquistation CSF34
198 Endress+Hauser
Ethernet and Modbus TCP
Signal encoding IEEE 802.3 (Ethernet)
Data transmission rate 10/100 MBd
Galvanic isolation Yes
Connection RJ45
IP address DHCP (default) or configuration via menu
Ethernet/IP
Signal encoding IEEE 802.3 (Ethernet)
Data transmission rate 10/100 MBd
Galvanic isolation Yes
Connection RJ45
IP address DHCP (default) or configuration via menu
PROFINET
Signal encoding IEEE 802.3 (Ethernet)
Data transmission rate 100 MBd
Galvanic isolation Yes
Connection RJ45
Name of station Via DCP protocol by means of configuration tool (e.g. Siemens
PRONETA)
IP address Via DCP protocol by means of configuration tool (e.g. Siemens
PRONETA)
Current outputs, active Span
0 to 23 mA
2.4 to 23 mA for HART communication
Signal characteristic
Linear
Signal on alarm
Adjustable, as per NAMUR Recommendation NE 43
In measuring range 0 to 20 mA (HART is not available with this measuring range):
Failure current from 0 to 23 mA
In measuring range 4 to 20 mA: Failure current from 2.4 to 23 mA
Factory setting for failure current for both measuring ranges: 21.5 mA
Load
Max. 500 Ω
Electrical specification
Output voltage
Max. 24 V

Table of Contents

Other manuals for Endress+Hauser Liquistation CSF34

Related product manuals