Electrical connection Liquistation CSF34
36 Endress+Hauser
6.4.5 Module ETH
 42 Module
Ethernet
DIP switch
on
1
2
4
8
16
32
64
128/SW
Service
COM
SF
BF
PWR
 43 Wiring
diagram
LEDs on front of module
LED Designation Color Description
RJ45 LNK/ACT GN Off = Connection is not active
On = Connection is active
Flashing = Data transmission
RJ45 10/100 YE Off = Transmission rate 10 MBit/s
On = Transmission rate 100 MBit/s
PWR Power GN Supply voltage is applied and module is initialized
BF Bus failure RD Not used
SF System failure RD Device error
COM Communication YE Modbus message sent or received
DIP switches on front of module
DIP Factory
setting
Assignment
1-128 ON Bus address (→ "Commissioning/communication")
OFF Write protection: "ON" = configuration not possible via the bus, only via local
operation
Service OFF If the switch is set to "ON" , the user settings for Ethernet addressing are saved
and connection settings programmed into the device at the factory are activated:
IP address=192.168.1.212, Subnet mask=255.255.255.0, Gateway=0.0.0.0,
DHCP=Off.
If the switch is set to "OFF" , the saved user settings are reactivated.