Operation Liquistation CSF34
64 Endress+Hauser
Menu/Setup/General settings/Logbooks
Function Options Info
Data logbooks
New You can create a maximum of 8 data logbooks.
Logbook name Customized text, 20
characters
Source of data Selection
Sensor inputs
Heartbeat signals
Controller
Current inputs
Temperature
Fieldbus signals
Binary inputs
Mathematical functions
Factory setting
None
Select a data source for the logbook entries.
You can choose from the following:
Connected sensors
Available controllers
Current inputs
Fieldbus signals
Binary input signals
Mathematical functions
Measured value Selection
Depends on Source of data
Factory setting
None
You can record different measured values
depending on the data source.
Scan time 0:00:01 to 1:00:00
Factory setting
0:01:00
Minimum time interval between two entries
Format: H:MM:SS
Data logbook Selection
Ring buffer
Fill up buffer
Factory setting
Ring buffer
Ring buffer
If the memory is full, the most recent entry
automatically overwrites the oldest entry.
Fill up buffer
If the memory is full, there is an overflow,i. e. no
new values can be saved. The controller displays
a corresponding diagnostic message. The
memory then has to be cleared manually.
Overflow warnings
Event logbook =
Fill up buffer
Selection
Off
On
Factory setting
Off
Decide whether you want to receive a
diagnostic message if the fill buffer of the
relevant logbook overflows.
Add another
logbook
Action Only if you want to create another data logbook
immediately. You add a new data logbook at a
later date using New.
Finished Action This allows you to exit the New menu.
Start/stop
simultaneously
Action Appears if you have created more than one data
logbook. With one mouse click, you can start or
stop recording all the data logbooks.
Logbook name The name of this submenu is based on the name
of the logbook and only appears once you have
created a logbook.
This menu appears several times if you have several data logbooks.