15.3 "Setup" menu
: Indicates navigation to the parameter via operating tools
: Indicates parameters that can be locked via the access code.
Navigation Setup
Device tag
Navigation Setup → Device tag
Description Enter a unique name for the measuring point to identify the device quickly within the
plant.
User entry Character string comprising numbers, letters and special characters (#32)
Factory setting EH_FMR20_####### (last 7 digits of the device serial number)
Distance unit
Navigation Setup → Distance unit
Description Used for the basic calibration (Empty / Full).
Selection
SI units
m
US units
ft
Empty calibration
Navigation Setup → Empty calibr.
Description Distance between process connection and minimum level (0%).
User entry 0.0 to 20 m
Factory setting Depends on the antenna version
Full calibration
Navigation Setup → Full calibr.
Description Distance between minimum level (0%) and maximum level (100%).