Operating menu Micropilot FMR20 HART
98 Endress+Hauser
15.4.2 "Simulation" submenu
Navigation  Diagnostics → Simulation
Simulation
Navigation Diagnostics → Simulation → Simulation
Description Select process variable to be simulated.
The Simulation is used to simulate specific measuring values or other conditions. This
helps to check the correct configuration of the device and connected control units.
Selection Off
Current output
Distance
Value current output
Navigation Diagnostics → Simulation → Value curr.out 1
Description Defines the value of the simulated output current.
User entry 3.59 to 22.5 mA
Process variable value
Navigation Diagnostics → Simulation → Proc. var. value
Description Value of the simulated process variable.
Downstream measured value processing and the signal output use this simulation value. In
this way, users can verify whether the measuring device has been configured correctly.
User entry 0 to 21.8 m