Commissioning and operation Micropilot FMR20 HART
36 Endress+Hauser
9.4 Configuring level measurement via operating
software
A0045565
31 Configuration parameters for level measurement in bulk solids
R Reference point of measurement
D Distance
L Level
E Empty calibration (= zero point)
F Full calibration (= span)
BD Blocking distance
9.4.1 Via SmartBlue
1. Navigate to: Setup → Distance unit
Select unit of length for distance calculation
2. Navigate to: Setup → Empty calibration
Specify empty distance E (distance from reference point R to minimum level)
3. Navigate to: Setup → Full calibration
Specify full distance F (span: max. level - min. level)
4. Navigate to: Setup → Distance
Shows the distance D that is currently measured from the reference point (lower
edge of flange / last sensor thread) to the level
5. Navigate to: Setup → Confirm distance
Compare the distance displayed with the actual value in order to start the
recording of an interference echo map
6. Navigate to: Setup → Mapping end point
This parameter determines the distance up to which the new mapping is to be
recorded
7. Navigate to: Setup → Present mapping
Displays the distance up to which a mapping has already been recorded
8. Setup → Confirm distance
9. Navigate to: Setup → Level
Shows the level L measured
10. Navigate to: Setup → Signal quality
Displays the signal quality of the analyzed level echo