Micropilot FMR20 HART Operating menu
Endress+Hauser 77
User entry 0.0 to 20 m
Factory setting Depends on the antenna version
Distance
Navigation Setup → Distance
Description Shows the distance D that is currently measured from the reference point (lower edge of
flange / last thread of sensor) to the level.
User interface 0.0 to 20 m
Level
Navigation Setup → Level
Description Displays the measured level L (before linearization).
The unit is defined in the 'Distance unit' parameter (factory setting = m).
User interface –99 999.9 to 200 000.0 m
Signal quality
Navigation Setup → Signal quality
Description Displays the signal quality of the level echo.
Meaning of the display options
- Strong:
The evaluated echo exceeds the threshold by at least 10 dB.
- Medium:
The evaluated echo exceeds the threshold by at least 5 dB.
- Weak:
The evaluated echo exceeds the threshold by less than 5 dB.
- No signal:
The device does not find an usable echo.
The signal quality indicated in this parameter always refers to the currently evaluated
echo, either the level echo or the tank bottom echo.
In case of a lost echo ('Signal quality' = No signal) the device generates the following error
message:
'Diagnostic echo lost' = Warning (factory setting) or Alarm, if the other option has been
selected in 'Diagnostic echo lost'.