Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 147
L
L
A
1.1
2.1
1.3
1.2
2.2 2.4
2.5
2.7
2.6
2.8
2.3
1.5
1.4
A
1
2
A0019641
 22 Configuration of the Advanced Diagnostics for foam detection
L Level
A Amplitude
1 Advanced diagnostics 1: Monitoring the level
1.1 "Assign diagnostic signal 1" = "Level linearized"
1.2 "Check mode 1" = "In range"
1.3 "Upper limit" = 85 %
1.4 "Lower limit" = 75 %
1.5 Digital output of Advanced Diagnostics 1
2 Advanced Diagnostics 2: Monitoring the amplitude
2.1 "Assign diagnostic signal 2" = "Relative echo amplitude"
2.2 "Calculation type 2" = "Mean"
2.3 "Sample time" = 60 s
2.4 "Check mode" = "Lower limit"
2.5 "Lower limit" = 10 dB
2.6 "Link AD 2 to" = "Digital output AD1"
2.7 "Linking logic AD 2" = "AND"
2.8 Digital output of Advanced Diagnostics 2