The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
116 Endress+Hauser
3.3 Expert → Output
3.3.1 Expert → Output → Switch output
Switch output function (0481)
Navigation Expert → Output → Switch output → Switch output function
Description Defines the function of the switch output (open collector).
Options Off
The output is always open (not conductive).
On
The output is always closed (conductive).
Event level
The output is normally closed and is only opened if a diagnostic event is present. The
Assign diagnostic level parameter (→  116)determines for which type of event the
output is opened.
Limit
The output is normally closed and is only opened if a measured varaible exceeds or falls
below a defined limit. The limit values are defined by the parameters Assign
limit(→  116), Switch-on value(→  117)and Switch-off value(→  117).
Digital output
The switching state of the output tracks the output value of a DI function block or the DI
output of the advanced diagnostics. The function block is selected in the Assign status
parameter.
Factory setting Off
Assign diagnostic level (0482)
Navigation Expert → Output → Switch output → Assign diagnostic level
Prerequisite Only visible for Switch output function = Event level.
Description Defines to which class of diagnostic events the output reacts.
Options Alarm
Alarm + warning
Warning
Factory setting Alarm
Assign limit (0483)
Navigation Expert → Output → Switch output → Assign limit