3.2.16 Expert → Sensor → External input
The External input submenu is only available on devices with PROFIBUS PA or
FOUNDATION Fieldbus.
Overview
The behavior of the sensor can be controlled via two external switch inputs: measurement
can be switched on and off. Furthermore, a specific value can be assigned to the level when
the digital switch signal is present, regardless of the actual filling height.
The parameters
Level external input 1/2 (2305/2306)
Navigation Expert → Sensor → External input → Level external input 1/2
Write permission Maintenance
Description External input 1 or 2 is assigned a DO block via which the switch signal is read in.
Options None
Digital output 1
Digital output 2
Digital output 3
Digital output 4
Factory setting None
Function input 1/2 level (2311/2331)
Navigation Expert → Sensor → External input → Function input 1/2 level
Write permission Maintenance
Description Defines the response of the level to the presence of a switch signal at external input 1 or 2.
Options Off
Minimum (0%)
Maximum (100%)
Hold last value
Fixed value
Factory setting Off
Fixed value input 1/2 (2332/2333)
Navigation Expert → Sensor → External input → Fixed value input 1/2