Endress+Hauser 45
3.2.4 Expert → Sensor → Level
Overview
The Level submenu is used to parametrize the calculation of the level from the measured
distance.
D0 D
L0
L
1 2
3
4
5
L
t
100%
B
0%
A
0%
100%
DL
B
A
0%
100%
E
D
L0
F
D0
R
D
DD
A0016141
1 Calculation of the level from the measured distance
1 Correction of the measured distance
2 Level calculation
3 Level limitation
4 Correction of the level
5 Definition of the output value: Level (A) or Ullage (B)
Parameters of the "Level" submenu
Task Required parameters Parameter Description
Correction of the measured distance Distance offset (2309) (→ 46)
Distance (2231) (→ 46)
Level calculation Empty calibration (2343) (→ 47)
Full calibration (2308) (→ 48)
Level unit (0576) (→ 49)
Level limitation Level limit mode (2314) (→ 50)
High limit (2312) (→ 50)
Low limit (2313) (→ 51)
Level correction Level correction (2325) (→ 51)
Definition of the output value Output mode (2317) (→ 52)
Level indication Level (2319) (→ 52)
Level linearized (2318) (→ 53)
Definition of the tank or silo height Tank/silo height (→ 53)