Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 49
Additional information The full calibration F is the distance between
the minimum level (0%) and the maximum
level (100%).
A0019487
F
0%
100%
A0019489
Level unit (0576)
Navigation Expert → Sensor → Level → Level unit
Write access Maintenance
Description Defines the level unit
Options %
m
mm
ft
in
Factory setting %
Additional information The level unit may differ from the distance unit defined in the Distance unit parameter
(→  38):
The distance unit is used for the basic calibration ("Empty calibration" and "Full
calibration").
The level unit is used to display the (unlinearized) level.