Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 51
Input range Depending on the selected distance unit:
• 0.0 to 100.0 %
• 0.0 to +200.0 m
• 0.2 to +656.2 ft
• 0.0 to +7874.0 inch
• 00.0 to +200,000.0 mm
Factory setting 100%
Additional information Levels exceeding the value specified in this parameter will be ignored. Instead, the device
uses the value specified in this parameter (for measured value transformation and output).
Low limit (2313)
Navigation Expert → Sensor → Level → Low limit
Write access Maintenance
Prerequisite Level limit mode = Low limit or Low and high limit
Description Defines the lower limit of the level signal.
Input range Depending on the selected distance unit:
• 0.0 to 100.0 %
• 0.0 to +200.0 m
• 0.0 to +656.2 ft
• 0.0 to +7874.0 inch
• 00.0 to +200,000.0 mm
Factory setting 0%
Additional information Levels falling below the value specified in this parameter will be ignored. Instead, the
device uses the value specified in this parameter (for measured value transformation and
output).
Level correction (2325)
Navigation Expert → Sensor → Level → Level correction
Write access Maintenance
Description Defines a level correction
Input range Depending on the selected level unit:
• -100.0 to 100.0 %
• -200.0 to +200.0 m
• -656.2 to +656.2 ft
• -7874.0 to +7874.0 inch
• -200,000.0 to +200,000.0 mm