The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
54 Endress+Hauser
Write access Maintenance
Description Total height of the tank or silo as measured from the process connection.
Input range –999.999 to +999.999 m (–3 280 to +3 280 ft)
Factory setting 4 m (13.1 ft)
Additional information If the parametrized measuring range (Empty
calibration) differs significantly from the tank
or silo height, it is recommended to enter the
tank or silo height. On default, Tank/Silo
height is always equal to Empty calibration.
Example: Continuous level monitoring in the
upper third of a tank or silo.
0%
E
1
A0019867
E Empty calibration
1 Tank/Silo height
E
1
0%
A0019868
E Empty calibration
1 Tank/Silo height