The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
66 Endress+Hauser
Additional information
1
A0019961
1 Absolute echo amplitude in the envelope curve, measured in dB
Relative echo amplitude (1089)
Navigation Expert → Sensor→ Information → Relative echo amplitude
Write access Read-only parameter
Description Indicates the relative amplitude of the level echo, i.e. the difference between the level echo
and the echo threshold.
In the envelope curve display of FieldCare, the absolute echo amplitude is indicated
instead of the relative amplitude (see the number on the top right of the echo peak in
the example).
Additional information
1
A0019962
1 The relative echo amplitude is the difference between the weighting curve (blue) and the peak in the envelope
curve (red).