Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 77
Dependencies of the "Integration time" parameter for "Medium type" = "Liquid"
Max. filling speed liquid Max. draining speed liquid
Slow
< 1cm (0,4in)/min
Medium
< 10cm (4in)/min
Standard
< 1m (40in)/min
Fast
< 2m (80in)/min
Very fast
> 2m (80in)/min
No filter / test
Slow
< 1cm (0,4in)/min
30 s 15 s 5 s 1 s 0 s 0 s
Medium
< 10cm (4in)/min
15 s 15 s 5 s 1 s 0 s 0 s
Standard
< 1m (40in)/min
5 s 5 s 5 s 1 s 0 s 0 s
Fast
< 2m (80in)/min
1 s 1 s 1 s 1 s 0 s 0 s
Very fast
> 2m (80in)/min
0 s 0 s 0 s 0 s 0 s 0 s
No filter / test 0 s 0 s 0 s 0 s 0 s 0 s
Dependencies of the "Integration time" parameter for "Medium type" = "Solid"
Max. filling
speed solid
Max. draining speed solid
Very slow
< 0,5m
(1,6ft)/h
Slow
< 1m (3,3ft)/h
Standard
< 2m (6,5ft)/h
Medium
< 4m (13ft)/h
Fast
< 8m (26ft)/h
Very fast
> 8m (26ft)/h
No filter / test
Very slow
< 0,5m
(1,6ft)/h
250 s 200 s 200 s 100 s 50 s 1 s 0 s
Slow
< 1m (3,3ft)/h
200 s 200 s 200 s 100 s 50 s 1 s 0 s
Standard
< 2m (6,5ft)/h
200 s 200 s 100 s 100 s 50 s 1 s 0 s
Medium
< 4m (13ft)/h
100 s 100 s 100 s 50 s 50 s 1 s 0 s
Fast
< 8m (26ft)/h
50 s 50 s 50 s 50 s 20 s 1 s 0 s
Very fast
> 8m (26ft)/h
1 s 1 s 1 s 1 s 1 s 1 s 0 s
No filter / test 0 s 0 s 0 s 0 s 0 s 0 s 0 s
Additional information Increasing the integration time results in a calmer measuring signal. However, this also
means that the measuring signal indicates level changes with a certain delay.