Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus The "Expert" menu
Endress+Hauser 81
Constant gas phase compensation factor
If the properties of the gas phase (pressure, temperature, composition) do not change over
the time and are known, a gas phase compensation can also be performed without a
reference signal. Instead, a constant, user-defined correction factor is applied in this case.
This factor is used to adjust the envelope curve and thus the measured echo distance.
A
B
B = FA
A0020199
 9 Gas phase compensation with a constant correction factor F
A Position of the level echo in the original envelope curve
B Position of the level echo in the corrected envelope curve.
Parameter Meaning Parameter description
GPC mode Select the Const. GPC factor option. (→  83)
Const. GPC factor Enter correction factor for distances (→  85)