The "Expert" menu Micropilot FMR50/FMR51/FMR52/FMR53/FMR54/FMR56/FMR57 FOUNDATION Fieldbus
94 Endress+Hauser
Factory setting Warning
Status in safety distance (11672)
Navigation Expert → Sensor → Safety settings → Status in safety distance
Write access Operator
Description Defines the status in case the safety distance is undershot.
Options • Good
• Uncertain
• Bad
Factory setting Bad
Acknowledge alarm (1130)
Navigation Expert → Sensor → Safety settings → Acknowledge alarm
Write access Maintenance
Prerequisite In safety distance = Self holding
Description Resets the self holding alarm of the device.
Options • No
The alarm is not rest.
• Yes
The alarm is reset. The measurement is resumed.
Factory setting No