Integration into a FOUNDATION Fieldbus network Micropilot FMR56, FMR57 FOUNDATION Fieldbus
48 Endress+Hauser
8.4.2 Block configuration when device is delivered
DIAGNOSTIC
PID ARITHMETIC SIGNAL_CHAR
S
RESOURCE
ANALOG_INPUT_1
ANALOG_INPUT_2
DI
ADV_SETUP
DATA_TRANSFER
EXPERT_INFO
SERVICE_INFO
DISPLAY
INPUT_SELECTOR
INTEGRATOR ANALOG_ALARM
EXPERT_CONFIG
SETUP
SERVICE_SENSOR
PV
SV
ESC
OPEN
OPEN
E
Device_01 F
mm
4841.000
A0017217
 17 Block configuration when device is delivered
S Sensor
PV Primary value: Level linearized
SV Secondary value: Distance
8.5 Assignment of the measured values (CHANNEL) in an AI Block
The input value of an Analog Input Block is defined by the CHANNEL parameter.
Channel Measured value
0 Uninitialized
211 Terminal voltage
773 Analog output advance diagnostics 1
774 Analog output advance diagnostics 2
32786 Absolute echo amplitude
32856 Distance
32885 Elektronic temperature