Micropilot FMR56, FMR57 FOUNDATION Fieldbus Commissioning (via operating menu)
Endress+Hauser 57
10.5 Configuration of a level measurement
A0016934
1. Setup → Device tag
Enter device tag.
2. Setup → Distance unit
Select distance unit.
3. Setup → Bin type
Select bin type.
4. Setup → Max. filling speed solid
Enter maximum expected filling speed.
5. Setup → Max. draining speed solid
Enter maximum expected draining speed.
6. Setup → Empty calibration
Enter empty distance E (Distance from reference point R to the 0% level)
3)
.
3) If the measuring range covers only an upper part of the tank or silo (E << tank/silo height), it is mandatory to
enter the acutal tank or silo height into the "Setup → Advanced Setup → Level → Tank/silo height" parameter. If
there is an outlet cone, the tank or silo height should not be adjusted as usually E is not << tank/silo height in
these applications.