Commissioning (block-based operation) Micropilot FMR56, FMR57 FOUNDATION Fieldbus
58 Endress+Hauser
7. Setup → Full calibration
Enter full distance F (Distance from the 0% to the 100% level).
8. Setup → Level
Indicates the measrued level L.
9. Setup → Distance
Indicates the measured distance from the reference point R to the level L.
10. Setup → Signal quality
Indicates the quality of the evaluated level echo.
11. Setup → Mapping → Confirm distance
Compare distance indicated on the display to real distance in order to start the
recording of an interference echo map.
12. Setup → Advanced setup →Level → Level unit
Select level unit: %, m, mm, ft, in (Factory setting: %)
It is strongly recommended to adjust the maximum filling and draining speed to the
actual process.
10.6 User-specific applications
For details of setting the parameters of user-specific applications, see separate
documentation:
BA01123F (Operating Instructions, FMR56/FMR57, FOUNDATION Fieldbus)
For the Expert submenu refer to:
GP01017F/00/EN (Description of Device Parameters, FMR5x, FOUNDATION Fieldbus)
11 Commissioning (block-based operation)
11.1 Block configuration
11.1.1 Preparatory steps
1. Switch on the device.
2. Note the DEVICE_ID → 44.
3. Open the FOUNDATION Fieldbus configuration program.
4. Load Cff and device description files into the host system or the configuration program.
Make sure you are using the right system files.
5. Identify the device using the DEVICE_ID (see Point 2). Assign the desired tag name to
the device by means of the Pd-tag/FF_PD_TAG parameter.
11.1.2 Configuring the Resource Block
1. Open the Resource Block.