Commissioning (block-based operation) Micropilot FMR56, FMR57 FOUNDATION Fieldbus
64 Endress+Hauser
Step Block Parameter Action
1 SETUP (TRDSUP) Distance unit (distance_unit) Select distance unit.
Selection:
1010: m
1013: mm
1018: ft
1019: in
2 SETUP (TRDSUP) Bin type (bin_type) Select bin type.
Selection:
734: Workbench test
1275: Bin/pile
1276: Buffer silo (fast)
1277: Crusher/belt
1278: Silo
3 SETUP (TRDSUP) Max. filling speed solid
(solid_filling_sped_range)
Select maximum expected filling speed.
Selection:
723: Very slow < 0,5m (1.6ft) /h
724: Slow < 1 m (3.3ft) /h
725: Medium < 4m (13ft) /h
726: Fast < 8m (26ft) /h
727: Very fast > 8m (26ft) /h
33442: No filter / test
4 SETUP (TRDSUP) Max draining speed solid
(solid_draining_sped_range)
Select maximum expected draining speed.
Selection:
723: Very slow < 0,5m (1.6ft) /h
724: Slow < 1 m (3.3ft) /h
725: Medium < 4m (13ft) /h
726: Fast < 8m (26ft) /h
727: Very fast > 8m (26ft) /h
33442: No filter / test
5 SETUP (TRDSUP) Empty calibration
(empty_calibration)
Enter the distance E between the reference
point R and the minimum level (0%).
6 SETUP (TRDSUP) Full calibration (full_calibration) Enter distance F between the minimum
(0%) and maximum (100%) level.
7 SETUP (TRDSUP) Level (level) Displays the measured level L.
8 SETUP (TRDSUP) Distance (filtered_dist_val) Displays the distance D between the
reference point R and the level L.