Levelflex M 3 Function group "basic setup" (00)
Endress+Hauser 21
3.11 Function "full calibr." (006)
This function is used to enter the distance from the minimum level to the maximum level (=span).
3.12 Display (008)
The distance measured from the reference point to the product surface and the meas. value cal-
culated with the aid of the empty adjustment are displayed. Check whether the values correspond
to the actual meas. value or the actual distance. The following cases can occur:
• Distance correct – meas. value correct -> continue with the next function,
"check distance" (051)
• Distance correct – meas. value incorrect -> Check "empty calibr." (005)
• Distance incorrect – meas. value incorrect -> continue with the next function,
"check distance" (051)
⇒
ENDRESS + HAUSER
E
+
–
100%
0%
F
F = full calibration (= span)
F
max
= E – upper blocking distance
⇒
ENDRESS + HAUSER
E
+
–