Levelflex M 8 Function group "output" (06), - "PROFIBUS param." (06), PROFIBUS PA only
Endress+Hauser 55
8.16 Function "select v0h0" (068), PROFIBUS PA only
Selects the value displayed in "measured value" (000).
Selection:
measured value
display value
measured value
The configured measured value is displayed in the "measured value" (000) function.
display value
The value in "display value" (069) is displayed in the "measured value" (000) function.
"
Caution!
This function is available for PROFIBUS PA devices only!
8.17 Function "20mA value" (069), HART only
In this function, enter the level (or volume, weight) at which the output current should be 20 mA.
This entry is only required if you have selected the
"current turn down" option in the "curr. output mode" (063) function.
8.18 Function "display value" (069), PROFIBUS PA only
This field can be set externally, e.g. from a PLC. The value is then displayed as the main measured
variable in the display by selecting the "select v0h0" (068) = "display value" function.
"
Caution!
This function is available for PROFIBUS PA devices only!