Levelflex M 3 Function group "basic setup" (00)
Endress+Hauser 23
"
Caution!
The range of mapping must end 0.3 m (20") before the echo of the actual level. In case of empty
vessel it is possible to make a map over the whole probe length.
probe free
If the probe is uncovered, mapping is carried out along the whole probe length.
"
Caution!
Only begin mapping in this function if the probe is safely uncovered. Otherwise, the device will not
make correct measurements.
3.14 Function "range of mapping" (052)
This function displays the suggested range of mapping. The reference point is always the reference
point of the measurement ( ä 1). This value can be edited by the operator.
For manual mapping, the default value is 0,3 m.
3.15 Function "start mapping" (053)
This function is used to start the interference echo mapping up to the distance given in "range of
mapping" (052).
Selection:
off: no mapping is carried out
on: mapping is started