Levelflex M 8 Function group "output" (06), - "PROFIBUS param." (06), PROFIBUS PA only
Endress+Hauser 53
8.11 Function "simulation" (065)
If necessary, linearisation, the output signal and the current output can be tested with the simulation
function. You have the following simulation options:
Selection:
sim. off
sim. level
sim. volume
sim. current (HART only)
sim. off
Simulation is switched off.
sim. level
Enter the level value in "simulation value" (066).
The functions
measured value (000)
measured level (0A6)
output current" (067) - only with HART instruments!
follow the entered values.
sim. volume
Enter the volume value in "simulation value" (066).
The functions
measured value (000)
output current" (067) - only with HART instruments!
follow the entered values.
sim. current (HART only)
Enter the current value in "simulation value" (066).
The function
output current" (067) - only with HART instruments!
follows the entered values.
ENDRESS + HAUSER
E
+
D
A
4...20 mA
0...100%
ENDRESS + HAUSER
E
+
sim. level
sim. volume
sim. current
(HART only)