4 Function group "safety settings" (01) Levelflex M
28 Endress+Hauser
hold
On echo loss, a warning is generated after a definable "delay time" (014). Output is held.
ramp %/min
On echo loss, a warning is generated after a definable "delay time" (014). The output is changed
towards 0% or 100% depending on the slope defined in "ramp %span/min" (013).
4.4 Function "ramp %span/min" (013)
Ramp slope which defines the output value on echo loss. This value is used if "ramp %span/min"
is selected in "outp. echo loss" (012). The slope is given in % of the measuring range per minute.