Levelflex M 6 Function group "linearisation" (04)
Endress+Hauser 37
!
Note!
After making entries into the table, activate it with "table on".
The 100% value (=20 mA for HART) is defined by the last point in the table.
!
Note!
Before confirming 0.00 m as the level or 0.00% as the volume, activate the Edit mode with
O or S.
Entries can be made into the linearisation table in ToF Tool using the table editor.
You can also display the contents graphically.
In addition, linearisation curves can be calculated for any tank shape.
Select the table point (Point 3).
Enter the level belonging to Point 3.
Enter the corresponding volume.
Enter a further table point?
Next table point.
...
Continue until "next point" (045) is answered with no.