Commissioning (installation and configuration) Proline Promag 300 HART
20 Endress+Hauser
5.4 Operation
For detailed information on the operating options, see the Operating Instructions.
5.5 Parameter configuration for safety-related applications
5.5.1 Adjustment of the measuring point
The measuring point is calibrated via the operating interfaces. A wizard guides you
systematically through all the submenus and parameters that have to be set for configuring
the measuring device.
For detailed information on the operating options, see the Operating Instructions.
For detailed information on configuring the measuring device, see the Operating
Instructions and Description of Device Parameters
Device protection
The devices can be protected against external influences as follows:
• Hardware write protection
• Software write protection
The application of these methods is described below.
5.5.2 Activation of SIL mode
To activate the SIL mode, the device must run through a confirmation sequence. While
running through this sequence, critical parameters are either set automatically by the device
to standard values or transferred to the local display/operating tool to enable verification of
the setting. On completion of parameter configuration, the SIL mode of the device must be
enabled with a SIL locking code.
Availability of the SIL mode function
NOTICE
The SIL confirmation sequence is only visible on the local display and in the operating
tools for devices with the order code for "Additional approval", option LA "SIL".
‣
For this reason, the SIL mode can also only be activated on these measuring devices.
‣
If the LA "SIL" option was ordered for the flowmeter ex works, this option is available when
the measuring device is delivered to the customer. Access is via the operating interfaces of
the measuring device.
‣
If the order option cannot be accessed in the measuring device, the function cannot be
retrofitted during the life cycle of the device. If you have any questions please contact your
Endress+Hauser service or sales organization.
Ways to check function availability in the measuring device:
Using the serial number:
Device viewer
1)
→ Order code for "Additional approval", option LA "SIL"
1) www.endress.com/deviceviewer