Proline Promag 300 HART Operation
Endress+Hauser 29
6. Enter the SIL locking code 7452.
If the SIL locking code has been entered correctly, the message "End of sequence"
appears on the display.
7. Press the  key to confirm.
The SIL mode is now deactivated.
6 Operation
6.1 Device behavior during power-up
Once switched on, the device runs through a start-up phase. The current output is set to
failure current during this time. This current is ≤ 3.6 mA in the initial seconds of this start-up
phase.
After that, depending on the setting of the "Start-up mode" parameter, the current is:
At the value MIN: ≤ 3.6 mA
At the value MAX: ≥ 21 mA
No communication with the device is possible via the interfaces during the start-up phase.
After the start-up phase the device switches to the normal mode (measuring operation).
6.2 Device behavior in safety function demand mode
The device outputs a current value corresponding to the limit value to be monitored. This
value must be monitored and processed further in a connected logic unit.
6.3 Safe states
The system adopts one of the three states depending on the error detected:
Application error
Application errors are detected by the device and a fixed failure current is output. The
device can continue communicating via HART (device state: "temporarily safe"). This state
persists until the application error is resolved and the device can again supply a valid
measured value at the current output. All parameters can be read.
Example: A cable open circuit is detected in the sensor.
Safe state / output current:
I ≤ 3.6 mA (low alarm)
I ≥ 21 mA (high alarm)
6.4 Device behavior in event of alarms and warnings
The output current on alarm can be set to a value ≤ 3.6 mA or ≥ 21 mA.
In some cases (e.g. a cable open circuit or faults in the current output itself, where it is not
possible to set the failure current ≥ 21 mA) output currents of ≤ 3.6 mA occur irrespective of
the configured failure current.