Proof testing Proline Promag 300 HART
30 Endress+Hauser
In some other cases (e.g. short circuit of cabling), output currents of ≥ 21 mA occur
irrespective of the configured failure current.
For alarm monitoring, the downstream automation system must be able to recognize both
maximum alarms (≥ 21 mA) and minimum alarms (≤ 3.6 mA).
6.5 Alarm and warning messages
Additional information is provided by the alarm and warning messages output in the form of
diagnostic events and associated event texts.
NOTICE
A diagnostic message is displayed even though the diagnostic event is no longer active in
the unlocked SIL mode.
When SIL mode is activated, additional diagnostics are activated. If a diagnostic event is
pending and the locked SIL mode is deactivated, the diagnostic message remains as long as
the error is still present.
In this case, the device must be disconnected briefly from the power supply .
When the device is then restarted, a self-check is carried out, and the diagnostics event is
reset where applicable.
This behavior occurs in the event of the following diagnostic message:
803 Current loop diagnostic message
After a period of 20 to 30 s, the diagnostic message changes from 803 Current loop
diagnostic message to F375 I/O- 1 to n communication failed diagnostic message. If
a check run in the device's event logbook confirms the previous 803 Current loop
diagnostic message diagnostic message, the installation must be checked for a cable
break.
7 Proof testing
The functional integrity of the device in the SIL mode must be verified during
commissioning, when changes are made to safety-related parameters, and also at
appropriate time intervals. The time intervals must be specified by the operator.
L
CAUTION
The safety function is not guaranteed during a proof test.
Suitable measures must be taken to guarantee process safety during the test.
The safety-related output signal 4 to 20 mA must not be used for the protective system
during the test.
Any test that is performed must be documented; the template in the appendix can be used
for this purpose →  47.
The operator specifies the testing interval and this must be taken into account when
determining the probability of failure PFD
avg
of the sensor system.
If no operator-specific proof testing requirements have been defined, the following is a
possible alternative for testing the transmitter depending on the measured variable used for