Proline Promag P 200
Endress+Hauser 7
Pulse/frequency/switch output
Function
Can be set to pulse, frequency or switch output
Version
Passive, open collector
Maximum input values
DC 35 V
50 mA
For information on the Ex connection values (® ä 9)
Voltage drop
For £ 2 mA: 2 V
For 10 mA: 8 V
Residual current
£ 0.05 mA
Pulse output
Pulse width
Adjustable:5 to 2 000 ms
Maximum pulse rate
100 Impulse/s
Pulse value
Adjustable
Assignable measured
variables
Volume flow
Mass flow
Frequency output
Output frequency
Adjustable:0 to 1 000 Hz
Damping
Adjustable:0 to 999 s
Pulse/pause ratio
1:1
Assignable measured
variables
Volume flow
Mass flow
Switch output
Switching behavior
Binary, conductive or non-conductive
Switching delay
Adjustable:0 to 100 s
Number of switching cycles
Unlimited
Assignable functions
Off
On
Diagnostic behavior
Limit value
Volume flow
Mass flow
Flow direction monitoring
Status
Empty pipe detection
Low flow cut off
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output
4-20 mA
Failure mode
Selectable (as per NAMUR recommendation NE 43):
Minimum value: 3.6 mA
Maximum value: 22 mA
Defined value:3.59 to 22.5 mA
Actual value
Last valid value
HART
Device diagnostics
Device condition can be read out via HART Command 48