Device Functions Proline Promass 80 10 Group PULSE/FREQUENCY OUTPUT
Endress+Hauser 35
SIMULATION
FREQUENCY
! Note!
This function is not available unless the FREQUENCY setting was selected in the
OPERATION MODE function.
Use this function to activate simulation of the frequency output.
Options:
OFF ON
Factory setting:
OFF
! Note!
• The “SIMULATION FREQUENCY OUTPUT” message indicates that simulation is
active.
• The measuring device continues to measure while simulation is in progress, i.e. the
current measured values are output correctly via the other outputs.
" Caution!
The setting is not saved if the power supply fails.
VALUE SIMULATION
FREQUENCY
! Note!
This function is not available unless FREQUENCY was selected in the OPERATION
MODE function and the VALUE SIMULATION FREQUENCY function is active (= ON).
Use this function to define a selectable frequency value (e.g. 500 Hz) to be output at the
frequency output. This value is used to test downstream devices and the measuring
device itself.
User input:
0...1250 Hz
Factory setting:
0 Hz
" Caution!
The setting is not saved if the power supply fails.
ASSIGN PULSE
! Note!
This function is not available unless the PULSE setting was selected in the OPERATION
MODE function.
Use this function to assign a measured variable to the pulse output.
Options:
OFF
MASS FLOW
VOLUME FLOW
CORRECTED VOLUME FLOW
Factory setting:
MASS FLOW
! Note!
If you select OFF, the only functions shown in this function group are ASSIGN PULSE
and OPERATION MODE.
Function description PULSE/FREQUENCY OUTPUT