8 Group HANDLING TOTALIZER
Function description HANDLING TOTALIZER
RESET ALL TOTALIZERS Use this function to reset the totals (including all overflows) of the totalizers (1...2) to
“zero” (= RESET).
Options:
NO
YES
Factory setting:
NO
! Note!
If the device has a status input and if it is appropriately configured, a reset for the totalizer
(1...2) can also be triggered by a pulse (see the ASS. STATUS INP. function ).
FAILSAFE MODE Use this function to define the response of all totalizers (1...2) to a fault.
Options:
STOP
The totalizer is paused until the fault is rectified.
ACTUAL VALUE
The totalizer continues to count based on the current flow measured value. The fault is
ignored.
HOLD VALUE
The totalizer continues to count the flow based on the last valid flow value (before the
fault occurred).
Factory setting:
STOP