13 Group COMMUNICATION Device Functions Proline Promass 80
48 Endress+Hauser
13 Group COMMUNICATION
Function description COMMUNICATION
TAG NAME Use this function to enter a tag name for the measuring device. You can edit and read this
tag name at the local display or via the HART protocol.
User input:
max. 8-character text, permissible: A-Z, 0-9, +, –, punctuation marks
Factory setting:
“_ _ _ _ _ _ _ _” (without text)
TAG DESCRIPTION Use this function to enter a tag description for the measuring device. You can edit and
read this tag description at the local display or via the HART protocol.
User input:
max. 16-character text, permissible: A-Z, 0-9, +, –, punctuation marks
Factory setting:
“_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _” (without text)
BUS ADDRESS Use this function to define the address for the exchange of data with the HART protocol.
User input:
0...15
Factory setting:
0
! Note!
Addresses 1...15: a constant 4 mA current is applied.
HART PROTOCOL Use this function to display if the HART protocol is active.
Display:
OFF = HART protocol not active ON = HART protocol active
! Note!
The HART protocol can be activated with the selection 4-20 mA HART or
4-20 mA (25 mA) HART in the CURRENT SPAN function (see Page 23).
MANUFACTURER ID Use this function to view the manufacturer ID in decimal numerical format.
Display:
Endress+Hauser
17 = (
11 hex) for Endress+Hauser
DEVICE ID Use this function to view the device ID in hexadecimal numerical format.
Display:
50 = (
80 dez) for Promass 80
DEVICE REVISION The device-specific revision of the HART command interface appears on the display.
Display:
e.g.: 5