Proline Promass 83, 84 ATEX II3G 0
Endress+Hauser 29
Terminal assignment and
connection data for signal
circuits with limited power
!
Note!
The following tables contain values/specifications, which are dependent on the type code (type of measuring
device). Please compare the following type code to the one shown on the nameplate of your measuring device.
A graphic representation of the electrical connections can be found: ä 28.
Terminal assignment of transmitter 83***-***********H+#**#
Terminal assignment of transmitter 83***-***********K+#**#
Terminal assignment and
connection data for signal
circuits (remaining
versions)
!
Note!
The following tables contain values/specifications, which are dependent on the type code (type of measuring
device). Please compare the following type code to the one shown on the nameplate of your measuring device.
A graphic representation of the electrical connections can be found: ä 28.
Terminal assignment
Transmitter
Terminal no. (inputs/outputs)
20 (+) 21 (–) 22 (+) 23 (–) 24 (+) 25 (–) 26 (+) 27 (–)
Assignment
–––
PROFIBUS PA
PA + PA –
Electric circuit Ex nA II or
Ex nL IIC
Safety-related
values
–––U
i
I
i
P
i
L
i
C
i
FNICO
35 V DC
600 mA
8.5 W
10 H
5 nF
Field device
Functional
values
galvanically isolated,
U
Bus
I
Bus
9 to 32 V DC
11 mA
IEC 61158-2 (MBP)
Transmitter
Terminal no. (inputs/outputs)
20 (+) 21 (–) 22 (+) 23 (–) 24 (+) 25 (–) 26 (+) 27 (–)
Assignment
–––
FOUNDATION
Fieldbus
FF + FF –
Electric circuit Ex nA II or
Ex nL IIC
Safety-related
values
–––U
i
I
i
P
i
L
i
C
i
FNICO
35 V DC
600 mA
8.5 W
10 H
5 nF
Field device
Functional
values
galvanically isolated,
U
Bus
I
Bus
9 to 32 V DC
12 mA
IEC 61158-2 (MBP)
Order
characteristic
"Inputs/outputs"
Terminal no. (inputs/outputs)
20 (+) 21 (–) 22 (+) 23 (–) 24 (+) 25 (–) 26 (+) 27 (–)
Non-convertible communication boards (fixed assignment)
A–
Pulse/frequency
output
Current output
HART
B Relay output 2 Relay output 1
Pulse/frequency
output
Current output
HART
J–
External termination PROFIBUS DP
1)
+5 V DGND B A
Q Status input
MODBUS RS485
1)
BA