Proline Promass F 100 Modbus RS485 Diagnostics and troubleshooting
81
Diagnostic
number
Short text Remedy instructions Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
046 Sensor limit exceeded 1. Inspect sensor
2. Check process condition
S Alarm
1)
062 Sensor connection 1. Change main electronic
module
2. Change sensor
F Alarm
082 Data storage 1. Check module connections
2. Contact service
F Alarm
083 Memory content 1. Restart device
2. Contact service
F Alarm
140 Sensor signal 1. Check or change main
electronics
2. Change sensor
S Alarm
1)
144 Measuring error too high 1. Check or change sensor
2. Check process conditions
F Alarm
1)
190 Special event 1 Contact service F Alarm
191 Special event 5 Contact service F Alarm
192 Special event 9 Contact service F Alarm
1)
Diagnostic of electronic
242 Software incompatible 1. Check software
2. Flash or change main
electronics module
F Alarm
270 Main electronic failure Change main electronic module F Alarm
271 Main electronic failure 1. Restart device
2. Change main electronic
module
F Alarm
272 Main electronic failure 1. Restart device
2. Contact service
F Alarm
273 Main electronic failure Change electronic F Alarm
274 Main electronic failure Change electronic S Warning
1)
311 Electronic failure 1. Reset device
2. Contact service
F Alarm
390 Special event 2 Contact service F Alarm
391 Special event 6 Contact service F Alarm
392 Special event 10 Contact service F Alarm
1)
Diagnostic of configuration
410 Data transfer 1. Check connection
2. Retry data transfer
F Alarm
411 Up-/download active Up-/download active, please
wait
C Warning
438 Dataset 1. Check data set file
2. Check device configuration
3. Up- and download new
configuration
M Warning
453 Flow override Deactivate flow override C Warning
484 Simulation failure mode Deactivate simulation C Alarm