10 Group CURRENT OUTPUT 1/2 Device Functions Proline t-mass 65
24 Endress+Hauser
10 Group CURRENT OUTPUT 1/2
Function description CURRENT OUTPUT 1/2
ASSIGN CURRENT Use this function to assign a measured variable to the current output.
Options:
OFF
MASS FLOW
CORRECTED VOLUME FLOW
TEMPERATURE
Factory setting:
MASS FLOW
! Note!
If you select OFF, the only function shown in this group is ASSIGN CURRENT function.
CURRENT SPAN Use this function to define the current span. The selection specifies the operational range
and the lower and upper signal on alarm. For the current output 1 the option HART can
be defined additionally.
Options:
0–20 mA
4–20 mA
4–20 mA HART (only current output1)
4–20 mA NAMUR
4–20 mA HART NAMUR (only current output1)
4–20 mA US
4–20 mA HART US (only current output1)
0–20 mA (25 mA)
4–20 mA (25 mA)
4–20 mA (25 mA) HART (only current output1)
Factory setting:
4–20 mA HART NAMUR (for current output 1)
4–20 mA NAMUR (for current output 2)
! Note!
The option HART is only supported by the current output designated as current output
1 in the device software, (terminals 26 and 27).
When switching the hardware from an active (factory setting) to a passive output sig-
nal select a current span of 4–20 mA (please refer to the Operating Instructions Proline
t-mass 65, BA111D/06/en)