Device Functions Proline t-mass 65 15 Group COMMUNICATION
Endress+Hauser 53
15 Group COMMUNICATION
Function description COMMUNICATION
TAG NAME Use this function to enter a tag name for the flowmeter. You can edit and read this tag
name at the local display or via the HART protocol.
User input:
max. 8-character text, permissible: A-Z, 0-9, +, –, punctuation marks
Factory setting:
“_ _ _ _ _ _ _ _” (without text)
TAG DESCRIPTION Use this function to enter a tag description for the flowmeter. You can edit and read this
tag description at the local display or via the HART protocol.
User input:
max. 16-character text, permissible: A-Z, 0-9, +, –, punctuation marks
Factory setting:
“_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _” (without text)
FIELDBUS ADDRESS Use this function to define the address for the exchange of data with the HART protocol.
User input:
0 to 15
Factory setting:
0
! Note!
Addresses 1 to 15: a constant 4 mA current is applied.
HART PROTOCOL Use this function to display if the HART protocol is active.
User interface:
OFF = HART protocol not active
ON = HART protocol active
! Note!
The HART protocol can be activated with the selection 4-20 mA HART resp.
4-20 mA (25 mA) HART in the CURRENT SPAN function (see page 24).
WRITE PROTECTION Use this function to check whether the flowmeter can be write-accessed.
User interface:
OFF = Data exchange is possible
ON = Data exchange disabled
Factory setting:
OFF
! Note!
Write protection is activated and deactivated by means of a jumper on the I/O module
(please refer to the Operating Instructions Proline t-mass 65, BA111D/06/en)
MANUFACTURER ID Use this function to view the manufacturer ID in decimal numerical format.
Display:
Endress+Hauser
17 = (
≅ 11 hex) for Endress+Hauser
DEVICE ID Use this function to view the device ID in hexadecimal numerical format.
Display:
101 = (
≅ 65 Hex) for t-mass 65