14 Group CURRENT INPUT Device Functions Proline t-mass 65
52 Endress+Hauser
VALUE SIMULATION
CURRENT INPUT
Use this function to specify a freely selectable value, e.g. 12 mA, which is to be simulated
at the current input. This value is used to test the current input function.
! Note!
This function is only available if the function SIMULATION CURRENT INPUT is
switched on.
User input:
0.00 to 25.00 mA
Factory setting:
0.00 mA or 4.00 mA (depending on the setting in function CURRENT SPAN, Page 50).
! Note!
If exiting this function and the SIMULATION CURRENT INPUT function is active (=
ON), the message END SIMULATION is displayed. Select YES to end simulation or NO
to continue simulation.
" Caution!
The setting is not saved in the event of a power failure.
Function description CURRENT INPUT