Device Functions Proline t-mass 65 14 Group CURRENT INPUT
Endress+Hauser 51
VALUE 20 mA Use this function to assign a value to the 20 mA current.
User input:
5-digit floating-point number
Factory setting:
Dependent on the process variable assigned to the current input (see function ASSIGN
CURRENT INPUT, Page 50).
Pressure: 21.000 [bar a] or 304.58 [psi a]
(country dependent,Page 71 ff.)
! Note!
The appropriate unit is taken from the group SYSTEM UNITS (see Page 9).
FAILSAFE VALUE Use this function to enter a defined error value for the process variable concerned. If the
current value lies outside of the selected range (see function CURRENT SPAN), then the
process variable is set to the "error value" defined here and a corresponding notice mes-
sage CURRENT INPUT RANGE (# 363) is generated.
User input:
5-digit floating-point number
Factory setting:
Dependent on the process variable assigned to the current input (see function ASSIGN
CURRENT INPUT).
Pressure: 1.0000 [bar a] or 14.504 [psi a]
(country dependent,Page 71 ff.)
! Note!
Triggered amplifier faults or the error behaviour of the outputs do not have any influ-
ence on the current input.
The appropriate unit is taken from the group SYSTEM UNITS (see Page 9).
ACTUAL CURRENT
INPUT
The actual value of the input current appears on the display.
User interface:
0.0 to 25 mA
SIMULATION CURRENT
INPUT
Use this function to activate the simulation of the current input.
Options:
OFF
ON
Factory setting:
OFF
! Note!
An active simulation is displayed by the notice message “SIM. CURR. IN” (# 661).
The value output for the simulation at the current input is defined in the function
VALUE SIMULATION CURRENT INPUT .
The flowmeter remains fully operational during the simulation and the current meas-
ured values are output correctly via the other outputs and the display.
" Caution!
The setting is not saved in the event of a power failure.
Function description CURRENT INPUT