11 Group PULSE/FREQUENCY OUTPUT Device Functions Proline t-mass 65
34 Endress+Hauser
SIMULATION
FREQUENCY
Use this function to activate simulation of the frequency output.
! Note!
This function is not available unless the FREQUENCY setting was selected in the OPERA-
TION MODE function.
Options:
OFF
ON
Factory setting:
OFF
! Note!
• The “SIMULATION FREQUENCY OUTPUT” message indicates that simulation is
active.
• The flowmeter continues to measure while simulation is in progress, i.e. the currently
measured values are output correctly via the other outputs.
" Caution!
The setting is not saved if the power supply fails.
VALUE SIMULATION
FREQUENCY
Use this function to define a selectable frequency value (e.g. 500 Hz) to be output at the
frequency output. This value is used to test downstream devices and the flowmeter itself.
! Note!
This function is not available unless FREQUENCY was selected in the OPERATION
MODE function and the VALUE SIMULATION FREQUENCY function is active (= ON).
User input:
max. 4-digit number: 0 to 1250 Hz
Factory setting:
0 Hz
! Note!
If exiting this function and the SIMULATION FREQUENCY function is active (= ON),
the message END SIMULATION is displayed. Select “YES” to end simulation or “NO” to
continue simulation.
" Caution!
The setting is not saved if the power supply fails.
ASSIGN PULSE Use this function to assign a measured variable to the pulse output.
! Note!
This function is not available unless the PULSE setting was selected in the OPERATION
MODE function.
Options:
OFF
MASS FLOW
CORRECTED VOLUME FLOW
Factory setting:
MASS FLOW
! Note!
If you select OFF, the only function shown in the CONFIGURATION function group is
this function, in other words ASSIGN PULSE.
Function description PULSE/FREQUENCY OUTPUT