11 Group PULSE/FREQUENCY OUTPUT Device Functions Proline t-mass 65
38 Endress+Hauser
OUTPUT SIGNAL
(continued)
Example for active output circuit (ACTIVE):
With an active circuit, the internal power supply is 24 V.
The pulse output is short-circuit proof.
a0004691
m = 24 V DC internal power supply
n = Short-circuit proof output
The signal levels are to be seen as analogous to the passive circuit.
The following applies for the output configuration ACTIVE-POSITIVE:
In the quiescent state (at zero flow), the output signal level at the terminals is 0 V.
a0004694
In the operating status (flow present), the output signal level changes from 0 V to a
positive voltage level.
a0004692
The following applies for the output configuration ACTIVE-NEGATIVE:
In the quiescent state (at zero flow), the output signal level at the terminals is at a positive
voltage level.
a0004693
In the operating status (flow present), the output signal level changes from a positive
voltage level to 0 V.
a0004710
Function description PULSE/FREQUENCY OUTPUT
+
-
=
1
5
8 3
7
U
t
24 V
0V
U
t
24 V
0V
U
t
24 V
0V
t
U
24 V
0V