12 Group RELAY OUTPUT 1/2 Device Functions Proline t-mass 65
44 Endress+Hauser
OFF-VALUE Use this function to assign a value to the switch-off point (relay output drops out). The
value can be greater or less than the switch-on point. Negative values are only permitted
for the measured variable TEMPERATURE.
! Note!
This function is not available unless LIMIT VALUE was selected in the ASSIGN RELAY
function.
User input:
5-digit floating-point number [unit]
Factory setting:
0 [kg/h; lb/h] or 0 [Nm
3
/h; Sm
3
/h] or +100 [°C]/+212 [°F]
(country dependent, Page 71 ff.)
! Note!
The appropriate unit is taken from the function group SYSTEM UNITS (see Page 9).
TIME CONSTANT Use this function to enter a time constant defining how the measuring signal reacts to
severely fluctuating measured variables, either very quickly (enter a low time constant) or
with damping (enter a high time constant). Damping acts on the measuring signal before
the switch status changes. The purpose of damping, therefore, is to prevent the relay out-
put changing state continuously in response to fluctuations in flow.
User input:
fixed-point number: 0.0 to 100.0 s
Factory setting:
0.0 s
ACTUAL STATUS RELAY Use this function to check the current status of the relay output.
A jumper on the contact side defines the relay output as normally open (NO or make) or
normally closed (NC or break) contact (please refer to the Operating Instructions Proline
t-mass 65, BA111D/06/en).
Display:
BREAK CONTACT OPEN
BREAK CONTACT CLOSED
MAKE CONTACT OPEN
MAKE CONTACT CLOSED
SIMULATION
SWITCH POINT
Use this function to activate simulation of the relay output.
Options:
OFF
ON
Factory setting:
OFF
! Note!
The “SIMULATION RELAY” message indicates that simulation is active.
The flowmeter continues to measure while simulation is in progress, i.e. the current
measured values are output correctly via the other outputs.
" Caution!
The setting is not saved if the power supply fails.
Function description RELAY OUTPUT 1/2