RIA14 Operation options
Endress+Hauser 15
2. Select the menu with "+" or "-"
3. Select the operating function
4. Enter parameters in editing mode (enter/select data with "+" or "-" and apply with "E")
5. Jump to the home position directly. You are first asked if the data entered until now
should be saved.
6. Exit the menu using "+ / - ". You are asked whether the data entered should be saved.
7. Confirm whether data should be saved. Select yes/no with the "+" or "-" operating key
and confirm with "E".
6.3 Structure and function of the operating menu
Menu Operating function Operating function Operating function
Parameter Default/
selection
Parameter Default/
selection
Parameter Default/
selection
Analog input
INPUT
Curve
CURV
Signal damping
DAMP
Decimal point for
measured value
DI DP
Linear LINAR 0 to 99 s 0 99.999 3 DEC
Squared SQRT 999.99 2 DEC
9 999.9 1 DEC
99 999 0 DEC
Measured value
scaling4 mA
DI LO
Measured value
scaling20 mA
DI HI
Measured value offset
OFFST
–
19 999 to 99
999
0.0 –
19 999 to 99
999
100.0 –
19 999 to 99
999
0.0
Display
DISPL
Dimension
DIM
Dimension
1)
DTEXT
None
%
Any
NO
%
TEXT
XXXXX
Limit
LIMIT
Measuring mode
MODE
Threshold
SETP
Off OFF –
19 999 to 99
999
0.0
Min. safety
with alarm
MIN
Max. safety
with alarm
MAX
Alarm ALARM
Hysteresis
HYST
Delay
DELY
–
19 999 to 99
999
0.0 0 to 99 s 0.0
Operating
parameters
PARAM
Operator code
CODE
Program name
PNAME
Firmware version
FWVER
0 to 9 999 0
NAMUR
NAMUR
NAMUR 3.6
2)
N_360
NAMUR 3.80
2)
N_380