RIA14 Commissioning
Endress+Hauser 17
Connecting the device
A0051931
10 Configuring the field indicator using an interface adapter
1 PC configuration software
2 Configuration kit USB box
3 Field indicator
When you connect the device, the device DTM (Device Type Manager) is not automatically
loaded in FieldCare, so you need to add the device manually.
Online configuration of parameters is not possible for the RIA14/16.
1. First add the Comm-DTM "PCP (Readwin) TXU10/FXA291" to an empty project.
2. In the Comm-DTM settings, set the baud rate to 2400 baud and select the COM port
used.
3. Add the device DTM "RIA14/16/Vx.xx.xx" to the project using the "Add device..."
function.
4. Continue with device configuration in accordance with these Operating Instructions.
The complete Setup menu, i.e. all of the parameters listed in these Operating
Instructions, can also be found in the FieldCareDevice Setup.
In general, it is possible to overwrite parameters with the FieldCare PC software and
the appropriate device DTM even if access protection is active. If access protection by
means of a code should be extended to the software, this function should be activated
in the extended device setup.
7 Commissioning
7.1 Post-installation check
Make sure that all installation and connection checks have been carried out before putting
the device into operation.
NOTICE
‣
Before commissioning the device, make sure that the supply voltage matches the
voltage specifications on the nameplate. Failure to perform these checks may result in
damage to the device caused by the incorrect supply voltage.