RIA14 Commissioning
Endress+Hauser 19
Designation Description
Measured value 100 %
'DI HI'
Indicates the display value for the 20 mA value.
Value range –19 999 to 99 999
Default: 100.0
Measured value offset
'OFFST'
Used to correct the display measured value. The offset is added to the measured value.
Value range –19 999 to 99 999
Default: 0.0
Measured value 0 % and 100 % should not be identical. However, the 0 % measured
value can be larger than the 100 % measured value (invert).
7.3.2 Display (DISPL)
Dimension
DIM → Options: NO, °C, K, °F, % or TEXT
You can choose one of the measurement units permanently stored in the display (°C, K, °F,
%). Alternatively, you can configure a unit of your choice on the 14-segment display
(TEXT).
The character set consists of the following characters: Characters A-Z, abcdhijlmnoruvwy,
the digits 0-9 and the special characters: - + * / ( ).
Configuring the editable unit (DTEXT)
DIM → DTEXT → Enter a unit that can be edited as required
To configure the editable unit, all 5 points on the 14-segment display must be configured.
Press the E key to edit the next letter. Accept the set unit with "E".
1.
2.
3.
4.
5.
E
E E E E
E
+/- +/- +/- +/- +/-
Esc
Esc
Esc
Esc
Esc
A0051908
Configuring the editable unit
1. Press the E key to select the desired operating function.
2. Press the E key to select the next point of the 5-digit 14-segment display.
3. Press the + or - key to select the next/previous character for the point selected.
4. If you press the +/- keys simultaneously, data entry is aborted and the operating
function is displayed.
5. When you confirm the fifth position of the display with E, the entry is accepted and
you switch to the operating function.